300/500 V 90°C 60227 IEC 07 (HIV)
SINGLE-CORE NON-SHEATHED CABLE WITH SOLID CONDUCTOR
Application
Use for general purpose
For installation in raceway and shall be protected water into raceway
Do not install in duct in ground or direct burial in ground
Construction
Conductor:Solid annealed copper
Insulation:Polyvinyl chloride(PVC). Black, Light Blue, Brown, Grey, Green/Yellow
or other colours
Reference Standard
TIS 11 Part 3-2553
Technical Characteristics
Maximum conductor temperature : 90°C
Rated voltage : 300/500 V
AC test voltage : 2,000 V
Conductor | Thickness of insulation | Overall diameter | Insulation resistance at 70 °C (Min.) | Current rating in free air | Cable weight (Approx.) | |||
---|---|---|---|---|---|---|---|---|
Cross-sectional area | No. of wires (Min.) | Diameter (Approx.) | Lower limit | Upper limit | ||||
mm2 | mm | mm | mm | mm | km | A | kg/km | |
0.5 | 1 | 0.79 | 0.6 | 1.9 | 2.3 | 0.015 | 3 | 9 |
0.75 | 1 | 0.96 | 0.6 | 2.1 | 2.5 | 0.013 | 6 | 11 |
1 | 1 | 1.11 | 0.6 | 2.2 | 2.7 | 0.012 | 10 | 14 |
1.5 | 1 | 1.36 | 0.7 | 2.6 | 3.2 | 0.011 | 16 | 21 |
2.5 | 1 | 1.75 | 0.8 | 3.2 | 3.9 | 0.009 | 25 | 33 |